Specification CPR main class Jacket Ø Single cable Ø Approx. Weight B2ca or Cca 8 fiber 16/32 48 64 96 12 fiber 24/48 72 96 144 mm 6.6 8.0 9.6 10.3 mm 2.0 2.0 2.0 2.0 numbered kg/km 46 70 93 108 Mechanical properties Tensile strength during installation in service Min. bend radius during installation in service Crush resistance short-term long-term Impact resistance Wp = 1.0 J Kink resistance r = 20 mm r = 30 mm N N mm mm N/dm N/dm impacts 600 4 x 100 90 60 5000 1000 50 p 800 6 x 100 110 70 5000 1000 50 p 1000 8 x 100 130 90 5000 1000 50 p 1400 12 x 100 150 100 5000 1000 50 p IEC 60794-1-2 E1 IEC 60794-1-2 E11 IEC 60794-1-2 E3 IEC 60794-1-2 E4 IEC 60794-1-2 E10 Thermal properties Temperature range during installation in service in storage °C −10 to +50 °C −20 to +70 °C −20 to +70 IEC 60794-1-22 F12 Combustion properties Fire load Fire propagation on a vertical single cable on a vertical cable bundle Smoke density Halogen acid gas jacket material Degree of acidity jacket material 2011/65/EC (RoHS) (EU) No 305/2011 (CPR) p = passed MJ/m 0.97 1.2 1.75 2.07 p p p p p p p p p p p p p p p p p p p p compliant B2ca-s1a,d0,a1 or Cca-s1a,d0,a1 IEC 60332-1-2 IEC 60332-3-25 IEC 61034-2 IEC 60754-1 IEC 60754-2 EN 50575 93