RADOX® UL 3271/CSA AWM I A/B Flexible single core • Excellent high and low temperature and ozone resistance • Weatherproof • Flame retardant • High resistance to heat pressure • High abrasion reistance • Easy to process • Soldering resistant • Flexible Application Protected and fixed installation inside electrical equipment, especially suitable for the connection of motor windings, switchboards, magnets and transformers. Composition of cable Conductor Insulation Core colours stranded tin plated copper, acc. to EN 60228, class 5 RADOX extruded and electron beam crosslinked polyolefin copolymer various, on request Technical data Voltage rating Test voltage Operating temperature Max. conductor temperature at short circuit (max. 5 s) Min. operating temperature flexing fixed 600 V AC 2500 V AC +125 °C +280 °C −25 °C −40 °C Standards Applicance wiring material Applicance wiring material CSA C22.2 no. 210.2 UL 758 AWM I A/B 125 °C 600 V FT2 style 3271 Approvals UL Underwriters Laboratories CSA Canadian Standards Association file no. E63322 certificate no.1418425 40 HUBER+SUHNER Wires and cables